User-friendly and simple measurements in the indoor gas installation in accordance with DVGW-TRGI 2018. Thanks to our long-standing experience in the field of pressure and leak measurements, we are now offering the third generation of our tried-and-tested measurement technology. The GasTest delta3 has significantly improved options for measurements on indoor gas installations. It also offers the option of service line tests via external pressure sensors.
Management of measurement data is possible via Esders Connect (optional)
Esders Connect is browser-based, so no updates are required, and you always have the latest version available.
Dimensions | 192 x 100 x 87 mm |
---|---|
Weight | approx. 1.160 g |
Operating temperature | 0 °C to +40 °C |
Measurement ranges | 0 - 300 mbar 0,1 mbar resolution, Error max. 0,5 % of full scale 0 - 1 bar 1 mbar resolution, Error max. 0,5 % of full scale 0 - 10 l/h 0,01 l/h resolution, Error max. 2,0 % of full scale |
Power supply | Li-ion battery pack, rechargeable, safe charging via charger with 230 V AC or 12 V DC |
Operating time | varies depending on the usage area and power consumption (e.g. usability according to G 5952 approx. 50 tests) |
Pump | integrated, flow approx. 40-45 l/h |
Display | LCD, 240 x 160 pixels, touch display for entering project numbers, address data, etc. |
Connection | 2 nipples (one to the reservoir, one to the installation) Connection for external, digital sensors (gas sensor, pressure sensor) |
Interface | Infrared & bluetooth |
Printing | via thermal printer (infrared or bluetooth) |
Data storage | > 2.000.000 measured values |
Certification | DVGW DG-4805DM0404 |