menu
Menu
Picture_Cable_HUNTER_devicePicture_Cable_HUNTER_Einsatz2Picture_Cable_HUNTER_EinsatzPicture_Cable_HUNTER_Alarm

Cable HUNTER

Navigation

Description

Easy cable fault location in low-voltage networks
Cable faults in the electricity network can often be difficult to locate. With our Cable HUNTER you can locate cable faults in the low-voltage network independently and immediately after the fault is reported, without any help from external cable measurement companies. The Cable HUNTER operates using two sensors that react to the gases emitted by burnt cable insulation material. When used in combination with the Vacuum Probe System 15 (VSS 15), it allows you to locate the fault quickly and easily.
The use of two sensors allows the system to differentiate between cable faults and natural gas or biogas.
Picture_Cable_HUNTER_Einsatz
Picture_Cable_HUNTER_Alarm

Features

  • Detection of cable faults while maintaining the power supply for consumers
  • Reduction of network downtime through avoidance of false excavations
  • Portable equipment with short-term payback
  • Reliable identification of the gases produced by burning cables

Technical data

DisplayLCD graphic display with 128 x 64 pixels,
illuminable Display of measured value and bar graph
Power supplyNiMH battery pack, 4.8 V, 3.8 Ah
Operating temperature-10 °C to +50 °C
Operating time
(without illumination))
> 10 hours including Bluetooth transmission
> 11 hours with no Bluetooth transmission
ChargingCharging cradle, via 12 V or 230 V supply
Charging time is approximately 3 to 5 hours
Data storageFlash memory with 4 MB for more than
100,000 measured values
Protection categoryIP54
Dimensions168 x 90 x 80 mm without connection couplings
Weightapprox. 1.100 g, including battery
Operating principleSpecialised semiconductor sensors
Response timeT90 ≤ 10 seconds
Pump capacity> 40 l/h, >300 mbar